4Ć175Target Data Configuration
Original Ć June 1990 CE4.2:CL6211
Absolute Pressure Conversion Ċ The value required to convert the
gauge pressure to absolute pressure, in engineering units. The
controller uses this value to calculate K for the Ideal Gas equation. The
valid range is any floating point value.
Absolute Temperature Conversion Ċ The value required to convert the
temperature to degrees Rankine or Kelvin. The controller uses this value
to calculate K for the Ideal Gas equation. The valid range is any floating
point value.
Gas Compensation Type Ċ This configuration item is used to select the
type of compensation; PRESSURE, TEMPERATURE or
PRESSURE/TEMPERATURE. This configuration item is only valid if
SQRT GAS FLOW, LINEAR GAS ORIFICE, or LINEAR GAS TURBINE has
been selected as the PT Compensation Type.
Intercept for Density Equation Ċ Represents the intercept of the
density curve. This configuration item is only valid if SQRT LIQ FLOW,
LINEAR LIQ ORIFICE, or LINEAR LIQ TURBINE have been selected as
the PT Compensation Type. The intercept may be any floating point
value.
Meter Calibration Density Ċ The value entered here should be taken
from the flow device specification sheet. The specification sheet should
have an operating condition for design density (density at flowing
conditions). This configuration item is only valid if SQRT LIQ FLOW,
LINEAR LIQ ORIFICE, or LINEAR LIQ TURBINE have been selected as
the PT Compensation Type. The valid range is any floating point value.
Meter Calibration Pressure Ċ The value entered here should be taken
from the flow device specification sheet. The specification sheet should
have an operating condition for design pressure (flowing pressure). The
controller expects this value to be relative, for example, PSIG as
opposed to PSIA. The units used also need to be consistent with the
units entered for absolute conversion. The valid range is any floating
point value.
Meter Calibration Temperature Ċ The value entered here should be
taken from the flow device specification sheet. The specification sheet
should have an operating condition for design temperature (flowing
temperature). The controller expects this value to be relative, for
example, DEG C as opposed to DEG K. The units used also need to be
consistent with the units entered for absolute conversion. The valid
range is any floating point value.
PT Compensation Type Ċ This configuration item is used to select the
type of compensation. The choices are SQRT GAS FLOW, LINEAR GAS
ORIFICE, LINEAR GAS TURBINE, SQRT LIQ FLOW, LINEAR LIQ
ORIFICE, and LINEAR TURBINE.
Pressure Source Ċ The pressure source is the tag of the point which
provides the pressure value to the pressure/temperature compensation
function. This tag may be up to twelve characters in length.