4Ć103FST Configuration
Original Ć June 1990 CE4.2:CL6211
IFTMAN IFTMAN
49
INSTRUCTION NAME: IFTMAN (if true set manual mode)
DESCRIPTION: This instruction places the loop being executed into the manual mode if the
discrete value in operand 1 is 1. If the discrete value is 0, the mode will not change. The SVA input
remains unchanged. Refer to section 5.6 on page 5Ć9 for more information on using this
instruction.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
RSP A M
T
M
OPERAND 1
NO GRAPHIC REPRESENTATION
CONFIGURATION FORMAT: IFTMAN (
Logic signal >>
Comment >>
OPERAND DESCRIPTIONS:
Logic signal - The name of the general register or discrete loadable function that contains the
discrete value.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVD(out) = SVD(in)
If discrete value = 1
Then mode = manual
If discrete value = 0
Then mode = no change
SVA(out) = SVA(in)