4Ć137FST Configuration
Original Ć June 1990 CE4.2:CL6211
PVLD PVLD
75
INSTRUCTION NAME: PVLD (process variable load)
DESCRIPTION: This instruction sets the SVA output equal to the value of the process variable
(PV) of the loop specified by operand 1. The process variable is the SVA input being used by the
PCA. The process variable value is converted from percent of span being used by the PCA to
engineering units (E.U.'s) using the engineering units low value (EULV) and the engineering units
high value (EUHV) of the loop specified by operand 1. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
%
!
EU
PV
REG
CONFIGURATION FORMAT: PVLD (
Loop tag >>
Comment >>
OPERAND DESCRIPTIONS:
Loop tag - The tag of the loop that contains the process variable value. The process variable
value is recalled from the process variable operating data register for the specified loop.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = (PV value)[(EUHV-EULV)/100] + EULV
SVD(out) = SVD(in)
Where: EULV = Engineering units low value
EUHV = Engineering units high value