4Ć50 FST Configuration
Original Ć June 1990CE4.2:CL6211
CASC CASC
14
INSTRUCTION NAME: CASC (cascade)
DESCRIPTION: This instruction provides cascade control linkage between two direct control
points, the second of which must have remote set point mode. The implied value position (IVP) of
the primary loop is automatically placed into the set point of the secondary loop when the
secondary loop is in the remote set point mode.
When the secondary loop is in the manual mode, the IVP of the primary loop tracks the process
variable of the secondary loop, if the primary loop is not in manual mode.
When the secondary loop is in the local automatic mode, the IVP of the primary loop tracks the local
set point of the secondary loop, if the primary loop is not in manual mode.
When the secondary loop is in the remote set point mode, the IVP of the primary loop becomes the
percent of span remote set point for the secondary control loop.
The primary loop will perform normal PID control action when the secondary loop is in the remote
set point mode as long as IVP of the secondary loop is not output limited. When the secondary
controller IVP is output limited, and the change in IVP of the primary control loop causes the
secondary loop to drive harder against its output limit, the integral action is disabled in the primary
loop. This prevents the primary loop from winding up its output when the secondary loop is already
output limited in the direction the primary loop is tending to drive it. The following guidelines apply
to the use of the cascade function:
H The primary loop must be set up for increase to open valves.
H The secondary loop must have the auto/manual/RSP station type.
H The cascade function cannot be used in the same loop as the TRK or OVRD functions.
H The secondary loop can use any of the PCA modifier functions.
H CASC can be used only once per direct control point.
CONFIGURATION FORMAT: CASC (
Loop tag >>
Track overrides manual enable>>
Comment >>
(Continued on next page)