Response Electronics CL6011B Specifiche Pagina 190

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 320
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 189
4Ć108 FST Configuration
Original Ć June 1990CE4.2:CL6211
INT INT
54
INSTRUCTION NAME: INT (integrator)
DESCRIPTION : This instruction takes the time integral of the SVA input. The analog value
contained in operand 1 is the integral gain in units of repeats per minute. Operand 2 is an analog
value that is the SVA output when the integrator function is reset (initial condition). Operand 3 is a
discrete value that resets the function. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
100
0
t
0
t
1
INPUT OUTPUT
tt
t
432
t
0
t
1
tt
t
432
I
50
100
0
100
100
t
0
t
1
tt
t
432
0
100
-100
t
0
t
1
tt
t
432
0
T
OPERAND 2
OPERAND 3
CONFIGURATION FORMAT: INT (
Integrator gain >>
Initial condition >>
Reset signal >>
Comment >>
(Continued on next page)
Vedere la pagina 189
1 2 ... 185 186 187 188 189 190 191 192 193 194 195 ... 319 320

Commenti su questo manuale

Nessun commento