5-8 Controller Cards
UM4.6:CS6003 Original — December 1991
5.2.1.2 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the MPU card shown in Figure 5-4, in the test slot
labeled MPU. If a discrete I/O card shown in Figure 5-5, is
present, insert it in the test slot labeled DIO. Ensure the
switch on the front of the MPU card is in the UP position.
X00816–A
Figure 5-4. Type CL6011 Interactive Controller MPU Unit
X00817–A
Figure 5-5. Type CL6011 Interactive Controller Discrete I/O Card
Step 3: Set the calibrator ON/OFF switch to ON.